ShUN/V prot. R3

The ShUN/V prot. R3 addressable fire-fighting control cabinet is designed to control a drain pump’s electric drive, a jockey pump, a fire-fighting pump, and a combined extract and input ventilation fan or a smoke exhaust fan within the addressable systems controlled by “Rubezh-2OP” prot.R3 fire alarm control panel or independently.
Operating mains voltage
230 (+23/-35) V
400 (+40/–60) V
Rated frequency 50 ±1 HZ
Auxiliary power consumption from mains, no more than 100 VÀ
Grounding type (selected with a jumper)
TN-C/ÒN-S
Ingress protection rating IP 31 (IP 54 upon the customer's request)

Overall dimensions:
Fire-fighting control cabinet

ShUN/V prot. R3 with a capacity of 0.18 to 45 kW
ShUN/V prot. R3 with a capacity of 55 to 110 kW
ShUN/V prot. R3 with a capacity of 132 to 185 kW
ShUN/V prot. R3 with a capacity of 220 to 250 kW

510 õ 410 õ 250 mm
810 õ 660 õ 270 mm
450 õ 600 õ 1600 mm
450 õ 800 õ 1600 mm

Weight, no more than:
Fire-fighting control cabinet

ShUN/V prot. R3 with a capacity of 0.18 to 15 kW
ShUN/V prot. R3 with a capacity of 18 to 45 kW
ShUN/V prot. R3 with a capacity of 55 to 110 kW

12 kg
17 kg
45 kg
Average service life, at least 10 years
Operating temperature range îò -25 (- 30 upon the customer's request) to +55°Ñ

ShUN/V prot. R3 fire-fighting control cabinet controls the electric drive via the magnetic contactor. Magnetic contactor on/off switching can be done in automatic control mode of by the built-in controller by a signal from the addressable fire alarm system panel and manually, using cabinet control buttons, without controller.

ShUN prot.R3 valve control cabinet ensures operation with three-phase electric motors with a rated power of 0.18 kW to 250 kW; or single-phase electric motors with a rated power of 0.18 kW to 3 kW.

Depending on the application, the ShUN prot.R3 valve control cabinet is able to control the following units:
  • fire pump; 
  • drain pump; 
  • jokey pump; 
  • fan.

The ShUN prot.R3 valve control box provides the following functions:

  • power supply at the network input availability and parameters control;

  • monitoring of main circuits of the unit's electric diagram; 
  • open-fault and short-circuit monitoring of input circuits from sensors and electric contact pressure gauges;
  • drive's power supply circuit monitoring;
  • local switching of the drive control mode to one of 3 modes: Automatic / Manual / Off;
  • transmission the own state signals via a RS-R3 digital communication line to the addressable fire alarm system control panel;

  • control of the connected electric drive according to commands received via a RS-R3 digital communication line from the addressable fire alarm system control panel, upon commands of level sensors, or upon local control commands.

ShUN/V prot. R3 fire-fighting control cabinet has the following control modes:

  •  “Automatic” - when the drive operation is provided by commands from the addressable fire alarm system control panel.

  • “Manual” - when operation of the motor is controlled from the control panel with Start and Stop buttons.

  • “Off” - when the contactor is de-energized, and the motor start is impossible.

The ShUN/V prot. R3 firefighting control cabinet is represented by a square metal enclosure containing the following devices:

1 - controller;
 2 - incoming switch;
3 - contactors;
4 - three-phase monitor relay;
 5- terminals for external circuits connection;
 6 - audible warning device;
 7 - CONTROL switch;
 8 - indication board.


ØÓÍ/Â ïðîò.R3

The ShUN/V prot. R3 fire-fighting control cabinet’s type of control is provided from the “Rubezh-2OP” prot. R3 panel when configuring the cabinet’s parameters or set via “FireSec Administrator” software.

In order to ensure the alarm circuit integrity control, resistors provided in the scope of supply shall be included into the scheme. The resistors shall be connected in close proximity to the sensors.